Skip to Content

VFD-EC-G120

Enclosed VFD
Siemens G120

A pre-engineered enclosed drive package built around the SINAMICS G120, released to a drawing and built to UL 508A. Thirteen motor ratings from 2 to 75 HP at 480 V, across five frame sizes, each with a door-interlocked disconnect, 24 V control power and a door-mounted IOP-2. Choose a NEMA 12 or NEMA 3R enclosure, and add Hand/Off/Auto with a speed potentiometer or a contactor bypass. Built in North Carolina and supplied with the shop drawings and bill of material it was built from.

  • 2 to 75 HPthirteen ratings, five frame sizes
  • NEMA 12 or 3Rindoor industrial or outdoor rainproof
  • IOP-2 on the doorset up and diagnose without opening up
  • Hand/Off/Auto optionselector and speed potentiometer on the door
  • Bypass contactor optionkeep the motor running while the drive is out
  • Built to UL 508Anameplate and listing label fitted
Keypad only
Hand / Off / Auto and speed pot
Bypass contactor option

Door layouts and the bypass arrangement are shown schematically. Actual device positions, cutout dimensions and the wiring as built are given on the released drawing set for the frame size you order.

Frame sizes

Frame A / B WALL

Saginaw EL wall-mount enclosure with a galvanized subpanel and a filtered fan. The compact end of the range.

  • Frame A · 2 and 4 HP30 × 24 × 10 in · drawing D10077
  • Frame B · 5, 7.5 and 10 HP30 × 24 × 16 in · drawing D10078

Frame C WALL

The same wall-mount arrangement in a deeper, taller box to take the larger power module and its contactors.

  • Frame C · 15 and 20 HP36 × 24 × 16 in · drawing D10079
  • Feed-through terminalsPT 6-QUATTRO on the power side

Frame D / E FLOOR

Saginaw XM floor-mount enclosure with a power distribution block, a 250 VA control transformer and a Max-Flex through-door breaker operator.

  • Frame D · 25, 30, 40 and 50 HP72 × 28 × 18 in · drawing D10080
  • Frame E · 60 and 75 HP72 × 28 × 18 in · drawing D10074

Frame size follows from the motor rating you select — you do not order it separately. Enclosure dimensions are the Saginaw catalogue sizes for the box used on each drawing.

At a glance

Motor ratings2 – 75 HP
Supply480 V, 3-phase, 60 Hz
DriveSINAMICS G120, PM240-2
Control unitCU240E-2 PN, Safety Integrated STO
Operator panelIOP-2, door mounted
NetworkPROFINET on the control unit
DisconnectThrough-door operator, interlocked
Control powerSITOP 24 V DC, 5 A
Motor protectionThermal overload relay, sized to rating
Thermal managementFiltered fan and thermostat
Enclosure ratingNEMA 12, or NEMA 3R
Enclosure makeSaginaw EL or XM
Local controlHand/Off/Auto and speed pot, optional
BypassContactor bypass, optional
Network accessRJ45 bulkhead, on request
Panel standardUL 508A industrial control panel
Released drawing setshop drawings and BOM supplied
UL 508Abuilt and labelled in-house
Quality manufacturersSiemens drive, Saginaw enclosure
North Carolinaengineered, built and supported
3 year warrantyon standard product

Enclosed Drive Package (Siemens G120) – 480V – 2 to 75 HP

https://think-plc.com/web/image/product.template/329448/image_1920?unique=2c5c628

Enclosed Drive Package (Siemens G120)

Part number family: VFD-EC-G120

A pre-engineered enclosed drive package built on the Siemens SINAMICS G120, released to a drawing and built to UL 508A. Thirteen motor ratings from 2 to 75 HP at 480 V, three phase, across five frame sizes. Each package includes the PM240-2 power module and CU240E-2 PN control unit, a door-mounted IOP-2, a door-interlocked disconnect with through-door operator, branch protection and a thermal overload relay sized to the rating, 24 V DC control power, and filtered forced-air cooling.

Configuration

· Motor rating — 2, 4, 5, 7.5, 10, 15, 20, 25, 30, 40, 50, 60 or 75 HP. The frame size and enclosure follow from the rating; you do not select them separately.

· Enclosure — NEMA 12 for indoor industrial areas with dust, dirt and dripping non-corrosive liquids, or NEMA 3R for outdoor rainproof service.

· Operator control — IOP-2 keypad only, or IOP-2 with a Hand/Off/Auto selector and speed potentiometer on the door.

· Bypass — drive only, or with a mechanically interlocked bypass contactor arrangement so the motor can be run across the line while the drive is out of service.

Frames A to C (2 to 20 HP) use a Saginaw EL wall-mount enclosure. Frames D and E (25 to 75 HP) use a Saginaw XM floor-mount enclosure and add a power distribution block, a 250 VA control transformer and a Max-Flex through-door breaker operator.

Each unit is built to a released drawing and ships with the shop drawings and bill of material it was built from.

Ordering: Standard configurations are available for direct online purchase. For purchase orders, custom modifications or application support, contact THINK-PLC to configure the solution to your requirements.

Freight is billed separately and is not included at checkout. We will contact you after your order with a freight quote and delivery options; shipment is scheduled after approval. All products are made to order and lead times vary with specification and order volume.

5,659.98 5659.98 USD 5,659.98 Tax Excluded

Call for price

  • Voltage
  • Horsepower (HP)
  • Enclosure Rating
  • Control Options
  • Bypass Option

This combination does not exist.

UL 508A Built in the USA 3 Year Warranty
Voltage: 480V